1.
Which description best matches a valid District Metered Area (DMA)?
An area defined only by customer billing addresses.
A network area with a pressure logger, regardless of unmeasured connections.
An area drawn in GIS with an inlet meter, regardless of boundary status.
A field-verified network area with controlled boundaries, where all water transfers and storage changes are measured or accounted for.
2.
GIS shows a DMA boundary valve as closed, but its actual position has not been verified. What should the team do before relying on the monitoring data?
3.
A proposed DMA meter can measure peak flow, but its low-flow capability has not been checked. What is the correct action?
4.
What must be in place before carrying out a controlled DMA boundary or connectivity test?
Utility authorisation, an approved procedure and agreed controls to protect supply, including critical customers.
Approval from the survey team alone, provided the test is short.
A completed GIS drawing, without operational approval.
Evidence of high night flow, which removes the need for further authorisation.
5.
A zone has one bulk inlet meter, two normally open interconnections shown only on an old drawing, and high minimum night flow. What is the correct conclusion?
The high night flow confirms leakage because the zone has an inlet meter.
All measured night flow can immediately be reported as recoverable leakage.
The old drawing is sufficient evidence that all water transfers are understood.
The high flow triggers investigation; the boundaries, flow paths, metering and operating configuration must be validated before concluding that it represents leakage.